NonStop NS-Series Planning Guide (H06.03+)

System Installation Planning
HP Integrity NonStop NS-Series Planning Guide529567-004
7-9
Power and Lighting
Section B:
B-
12
Supply Voltage Total Harmonic
Distortion? (THD)
Source 1 THD _______ %
Source 2 THD _______ %
B-
13
Capacity of input AC? (Source 1 KVA)
Customer supplied information.
B-
14
Capacity of input AC? (Source 2 KVA)
Customer supplied information.
B-
15
System load kW/kVA?
System load should be expressed as
kVA and kW sine the power factor is
significantly different from that of
most UPS.
B-
16
Distance from dedicated branch circuit
to equipment breaker?
Max HP recommended is 75 feet
[22.9 m]before circuit upgrade is
advised
B-
17
Describe Breaker and power feeds?
Rigid, EMT, Armoured Cable,
Liquidtite w/RFI strand, etc.
B-
18
Will power receptacle feed come from
an overhead raceway?
If so, is the raceway bonded and
grounded back to the power panel.
B-
19
How close are the light fixtures to the
sprinkler heads?
Local fire & safety codes may
stipulate a minimum spacing.
B-
20
Are light fixtures or any other objects
close enough to "swing" into sprinkler
heads in the event of an earthquake?
If light fixtures have enough travel
to swing into sprinkler heads, they
should be anchored to prevent
undesired contact.
VST036.vsd