NonStop NS-Series Planning Guide (H06.03+)

HP Integrity NonStop NS-Series Planning Guide529567-004
A-1
A Specifications
This appendix includes:
AC Input Power
Model R5500 XR Integrated UPS
Dimensions and Weights
Environmental Specifications
AC Input Power
North America and Japan: 208 V AC PDU Power Cords
Three-phase delta, four-wire with insulated ground conductor, 60A RMS
AC power cord (two supplied per modular cabinet): length 7 feet (183 centimeters)
AC power cable plug (one per power cord): four-wire, three-phase, 60A
°
HP Product ID: M8950-4
°
HP part number: 527993
°
Manufacturer: Hubbell
°
HP supplied plug manufacturer number: HBL460P9W
°
Required customer-supplied receptacle manufacturer number: HBL460C9W or
equivalent receptacle
Europe, Middle East, and Africa: 230/400 V AC PDU Power Cords
Three-phase wye, five-wire with insulated ground conductor, 63A RMS
AC power cord (two supplied per modular cabinet): length 7 feet (183 centimeters)
AC power cable plug (one per power cord): five-wire, three-phase, 63A
°
HP Product ID: M8950-5
°
HP part number: 527995
°
Manufacturer: Hubbell
°
HP supplied plug manufacturer number: HBL563P6W
°
Required customer-supplied receptacle manufacturer number: HBL563C6W or
equivalent receptacle
International: 200 to 250 V AC PDU Power Cords
Single-phase, three-wire with insulated ground conductor, 63A RMS
AC power cord (two supplied per modular cabinet): length 7 feet (183 centimeters)
AC power cable plug (one per power cord): three-wire, single-phase, 63A
Note. All specifications provided in this appendix assume that each enclosure in the modular
cabinet is fully populated; for example, a slice with four processors and maximum memory. The
maximum current for each AC service depends on the number and type of enclosures installed
in the modular cabinet. Power, weight, and heat loads are less when enclosures are not fully
populated; for example, in a slice with fewer processors or a disk drive enclosure with fewer
disks.