NonStop NS-Series Planning Guide (H06.05+)

System Installation Specifications
HP Integrity NonStop NS-Series Planning Guide529567-008
3-3
North America and Japan: 208 V AC PDU Power
North America and Japan: 208 V AC PDU Power
The PDU power characteristics are:
For additional information about the 208 V AC input, 3-phase delta, 24A RMS PDU
power option, refer to North America and Japan 208 V AC input, 3-phase delta, 24A
RMS Power on page 5-4.
North America and Japan: 200 to 240 V AC PDU Power
The PDU power characteristics are:
For additional information about the 200 to 240 V AC input, single phase, 40A RMS
PDU power option refer to North America and Japan 200 to 240 V AC input, Single
phase, 40A RMS Power on page 5-5.
PDU input
characteristics
208 V ac, 3-phase delta, 24A RMS, 4-wire
50/60Hz
NEMA L15-30 input plug
6.5 feet (2 m) attached power cord
PDU output
characteristics
3 circuit-breaker-protected 13.86A load segments
36 AC receptacles per PDU (12 per segment) - IEC 320 C13 10A
receptacle type
3 AC receptacles per PDU (1 per segment) - IEC 320 C19 12A
receptacle type
PDU input
characteristics
200 to 240 V ac, single phase, 40A RMS, 3-wire
50/60Hz
Non-NEMA Locking CS8265C, 50A input plug
6.5 feet (2 m) attached power cord
PDU output
characteristics
3 circuit-breaker-protected 20A load segments
36 AC receptacles per PDU (12 per segment) - IEC 320 C13 10A
receptacle type
3 AC receptacles per PDU (1 per segment) - IEC 320 C19 12A
receptacle type