NonStop NS-Series Planning Guide (H06.05+)
System Installation Specifications
HP Integrity NonStop NS-Series Planning Guide—529567-008
3-4
International: 380 to 415 V AC PDU Power
International: 380 to 415 V AC PDU Power
The PDU power characteristics are:
For additional information about the 380 to 415 V AC input, 3-phase Wye, 16A RMS
PDU power option, refer to International 380 to 415 V AC input, 3-phase Wye, 16A
RMS Power on page 5-5.
International: 200 to 240 V AC PDU Power
The PDU power characteristics are:
For additional information about the 200 to 240 V AC input, single phase, 32A RMS
PDU power option refer to International 200 to 240 V AC input, Single phase, 32A
RMS Power on page 5-6.
Grounding
A safety ground/protective earth conductor is required for each AC service entrance to
the NonStop server equipment. This ground must comply with local codes and any
other applicable regulations
PDU input
characteristics
•
380 to 415 V ac, 3-phase Wye, 16A RMS, 5-wire
•
50/60Hz
•
IEC309 5-pin, 16A input plug
•
6.5 feet (2 m) attached harmonized power cord
PDU output
characteristics
•
3 circuit-breaker-protected 16A load segments
•
36 AC receptacles per PDU (12 per segment) - IEC 320 C13 10A
receptacle type
•
3 AC receptacles per PDU (1 per segment) - IEC 320 C19 12A
receptacle type
PDU input
characteristics
•
200 to 240 V ac, single phase, 32A RMS, 3-wire
•
50/60Hz
•
IEC309 3-pin, 32A input plug
•
6.5 feet (2 m) attached harmonized power cord
PDU output
characteristics
•
3 circuit-breaker-protected 20A load segments
•
36 AC receptacles per PDU (12 per segment) - IEC 320 C13 10A
receptacle type
•
3 AC receptacles per PDU (1 per segment) - IEC 320 C19 12A
receptacle type