NonStop NS-Series Planning Guide (H06.05+)

System Installation Specifications
HP Integrity NonStop NS-Series Planning Guide529567-008
3-4
International: 380 to 415 V AC PDU Power
International: 380 to 415 V AC PDU Power
The PDU power characteristics are:
For additional information about the 380 to 415 V AC input, 3-phase Wye, 16A RMS
PDU power option, refer to International 380 to 415 V AC input, 3-phase Wye, 16A
RMS Power on page 5-5.
International: 200 to 240 V AC PDU Power
The PDU power characteristics are:
For additional information about the 200 to 240 V AC input, single phase, 32A RMS
PDU power option refer to International 200 to 240 V AC input, Single phase, 32A
RMS Power on page 5-6.
Grounding
A safety ground/protective earth conductor is required for each AC service entrance to
the NonStop server equipment. This ground must comply with local codes and any
other applicable regulations
PDU input
characteristics
380 to 415 V ac, 3-phase Wye, 16A RMS, 5-wire
50/60Hz
IEC309 5-pin, 16A input plug
6.5 feet (2 m) attached harmonized power cord
PDU output
characteristics
3 circuit-breaker-protected 16A load segments
36 AC receptacles per PDU (12 per segment) - IEC 320 C13 10A
receptacle type
3 AC receptacles per PDU (1 per segment) - IEC 320 C19 12A
receptacle type
PDU input
characteristics
200 to 240 V ac, single phase, 32A RMS, 3-wire
50/60Hz
IEC309 3-pin, 32A input plug
6.5 feet (2 m) attached harmonized power cord
PDU output
characteristics
3 circuit-breaker-protected 20A load segments
36 AC receptacles per PDU (12 per segment) - IEC 320 C13 10A
receptacle type
3 AC receptacles per PDU (1 per segment) - IEC 320 C19 12A
receptacle type