NonStop NS-Series Planning Guide (H06.05+)

Modular System Hardware
HP Integrity NonStop NS-Series Planning Guide529567-008
5-27
UPS and ERM (Optional)
UPS and ERM (Optional)
An uninterruptible power supply (UPS) is optional but recommended where a site UPS
is not available. You can use any UPS that meets the modular cabinet power
requirements for all enclosures being powered by the UPS. One UPS option is the HP
R5500 XR UPS. For information about the requirements for installing a UPS other than
the HP R5500 XR UPS in an Integrity NonStop NS-series system, see Uninterruptible
Power Supply (UPS) on page 2-3.
Cabinet configurations that include an R5500 XR UPS also have one extended runtime
module (ERM). An ERM is a battery module that extends the overall battery-supported
system run time. A second ERM can be added for even longer battery-supported
system run time.
Adding an R5500 XR UPS to a modular cabinet in the field requires removing the PDU
on the right side of the modular cabinet and installing HP extension bars that are
compatible with the UPS. A factory-installed UPS ships with the HP extension bars
already installed on the right side of the modular cabinet. The PDU and extension bars
are oriented inward, facing the components within the modular cabinet. Both the UPS
and the ERM are 3U high and must reside in the bottom of the cabinet.
This illustration shows the location of a UPS and an ERM in a modular cabinet:
Note. Retrofitting a system in the field with a UPS and ERMs will likely require moving all
installed enclosures up in the modular cabinet to provide space for the new hardware. One or
more of the enclosures that formerly resided in the modular cabinet might be displaced and will
therefore have to be installed in another modular cabinet that would also need a UPS and
ERMs installed. Additionally, lifting equipment might be required to lift heavy enclosures to their
new location.
Note. The AC input power cord for the R5500 XR UPS is routed to exit the modular cabinet at
either the top or bottom rear corners of the cabinet depending on what is ordered for the site
power feed, and the large output receptacle is unused.
VST504.vsd
Uninterruptible Power
Supply (UPS)
Extended Run Time
Module (ERM)
ERM - UPS Cable
12
12
Unused
Cable
To AC Power Source
To Extension Bars