NonStop NS-Series Servers Site Preparation (H06.03+)

HP Integrity NonStop NS-Series Site Preparation Guide527836-005
3-1
3
Specifications for Integrity NonStop
NS-Series Servers
This section includes:
Modular Cabinet AC Input Power
North America and Japan: 208 V AC PDU Power Cords
Europe, Middle East, and Africa: 230/400 V AC PDU Power Cords
International: 200 to 250 V AC PDU Power Cords
Grounding
Branch Circuits and Circuit Breakers
Enclosure AC Input
Modular Cabinet PDU Phase Distribution
Enclosure Power Loads
Model R5500 XR Integrated UPS
Model R5500 XR Integrated UPS
Dimensions and Weights
Plan View of the Modular Cabinet
Plan View of the Modular Cabinet
Service Clearances for the Modular Cabinet
Modular Cabinet Physical Specifications
Enclosure Dimensions
Modular Cabinet and Enclosure Weights With Worksheet
Environmental Specifications
Heat Dissipation Specifications and Worksheet
Operating Temperature, Humidity, and Altitude
Nonoperating Temperature, Humidity, and Altitude
Cooling Airflow Direction
Typical Acoustic Noise Emissions
Tested Electrostatic Immunity
Modular Cabinet AC Input Power
An AC power cable is factory-connected to each of two PDUs inside the modular
cabinet. When you order the system, you specify the factory-installed location of the
Note. All specifications provided in this section assume that each enclosure in the modular
cabinet is fully populated; for example, a slice with four processors and maximum memory. The
maximum current for each AC service depends on the number and type of enclosures installed
in the modular cabinet. Power, weight, and heat loads are less when enclosures are not fully
populated; for example, as a slice with fewer processors or a disk drive enclosure with fewer
disks.