NonStop NS-Series Servers Site Preparation (H06.03+)
HP Integrity NonStop NS-Series Site Preparation Guide—527836-005
3-1
3
Specifications for Integrity NonStop
NS-Series Servers
This section includes:
•
Modular Cabinet AC Input Power
•
North America and Japan: 208 V AC PDU Power Cords
•
Europe, Middle East, and Africa: 230/400 V AC PDU Power Cords
•
International: 200 to 250 V AC PDU Power Cords
•
Grounding
•
Branch Circuits and Circuit Breakers
•
Enclosure AC Input
•
Modular Cabinet PDU Phase Distribution
•
Enclosure Power Loads
•
Model R5500 XR Integrated UPS
•
Model R5500 XR Integrated UPS
•
Dimensions and Weights
•
Plan View of the Modular Cabinet
•
Plan View of the Modular Cabinet
•
Service Clearances for the Modular Cabinet
•
Modular Cabinet Physical Specifications
•
Enclosure Dimensions
•
Modular Cabinet and Enclosure Weights With Worksheet
•
Environmental Specifications
•
Heat Dissipation Specifications and Worksheet
•
Operating Temperature, Humidity, and Altitude
•
Nonoperating Temperature, Humidity, and Altitude
•
Cooling Airflow Direction
•
Typical Acoustic Noise Emissions
•
Tested Electrostatic Immunity
Modular Cabinet AC Input Power
An AC power cable is factory-connected to each of two PDUs inside the modular
cabinet. When you order the system, you specify the factory-installed location of the
Note. All specifications provided in this section assume that each enclosure in the modular
cabinet is fully populated; for example, a slice with four processors and maximum memory. The
maximum current for each AC service depends on the number and type of enclosures installed
in the modular cabinet. Power, weight, and heat loads are less when enclosures are not fully
populated; for example, as a slice with fewer processors or a disk drive enclosure with fewer
disks.