NonStop NS-Series Servers Site Preparation (H06.03+)
Specifications for Integrity NonStop NS-Series
Servers
HP Integrity NonStop NS-Series Site Preparation Guide—527836-005
3-2
North America and Japan: 208 V AC PDU Power
Cords
PDU junction boxes at the top or bottom of the modular cabinet, depending on what
the site provides for power feed:
•
Top feed: For power cables routed to the top of the modular cabinet (such as from
overhead cable trays)
•
Bottom feed: For power cables routed to the bottom of the modular cabinet (such
as from under raised flooring)
Each PDU powers 14 power receptacles per PDU (28 receptacles per modular
cabinet) that receive power cords from the installed enclosures.
North America and Japan: 208 V AC PDU Power Cords
•
Three-phase delta, four-wire with insulated ground conductor, 60A RMS
•
AC power cord (two supplied per modular cabinet): length 7 feet (183 centimeters)
•
AC power cable plug (one per power cord): four-wire, three-phase, 60A
°
HP Product ID: M8950-4
°
HP part number: 527993
°
Manufacturer: Hubbell
°
HP supplied plug manufacturer number: HBL460P9W
°
Required customer-supplied receptacle manufacturer number: HBL460C9W or
equivalent receptacle
PDUs
(bottom feed
shown)
VST071.vsd
Power Cables
In-Line Power
Connectors
(supplied with
cabinet)
Mating Socket
Connector
(customer-supplied)
Ground
VST051.vsd