Unit Sizes
Unit Sizes
Modular Cabinet PDU Keepout Panel
PDU keepout applies only when the PDU junction boxes reside at the bottom of the
modular cabinet. PDUs overlap the outside of the rack by 2 U (3.5 inches). A PDU
keepout panel is installed in affected space when:
•
1U keepout applies when a UPS occupies the bottom position of the modular
cabinet.
•
2U keepout applies when a processor slice occupies the bottom position of the
modular cabinet.
Modular Cabinet Physical Specifications
Enclosure Type Height (U)
Modular cabinet 42
Processor slice 5
Processor switch 3
LSU 4
IOAM 11
Disk drive 3
Maintenance switch (Ethernet) 1
R5500 XR UPS 3
Extended runtime module 3
PDU keepout panel
*
1 or 2
*
Rackmount Console 2
*
See Modular Cabinet PDU Keepout Panel
Item Height Width Depth Weight
in. mm in. mm in. mm
Modular cabinet 78.5 1994 23.5 597 44.0 1118 Depends on the
enclosures installed.
Refer to Modular
Cabinet and
Enclosure Weights
With Worksheet on
page 3-9.
Rack 78.5 1994 23.5 597 40.0 1020
Front door 78.5 1994 23.5 597 3.0 76
Left-rear door 78.5 1994 11.0 279 1.0 25
Right-rear door 78.5 1994 12.0 305 1.0 25
Shipping
(palletized)
83.5 2120 39.0 990 48.0 1220