NonStop NS-Series Servers Site Preparation (H06.03+)
Specifications for Integrity NonStop NS-Series
Servers
HP Integrity NonStop NS-Series Site Preparation Guide—527836-005
3-11
Nonoperating Temperature, Humidity, and Altitude
Nonoperating Temperature, Humidity, and Altitude
•
Temperature:
°
up to 72-hour storage: - 40° to 150° F (-40° to 66° C)
°
Up to 6-month storage: -20° to 131° F (-29° to 55° C)
°
Reasonable rate of change with noncondensing relative humidity during the
transition from warm to cold
•
Relative humidity: 10% to 80%, noncondensing
•
Altitude: 0 to 40,000 feet (0 to 12,192 meters)
Cooling Airflow Direction
Each enclosure includes its own forced-air cooling fans or blowers. Air flow for each
enclosure enters from the front of the modular cabinet and rack and exhausts at the
rear.
Typical Acoustic Noise Emissions
•
70 dB(A) (sound pressure level at operator position)
Tested Electrostatic Immunity
•
Contact discharge: 8 KV
•
Air discharge: 20 KV