NonStop NS-Series Servers Site Preparation (H06.03+)

Specifications for Integrity NonStop NS-Series
Servers
HP Integrity NonStop NS-Series Site Preparation Guide527836-005
3-11
Nonoperating Temperature, Humidity, and Altitude
Nonoperating Temperature, Humidity, and Altitude
Temperature:
°
up to 72-hour storage: - 40° to 150° F (-40° to 66° C)
°
Up to 6-month storage: -20° to 131° F (-29° to 55° C)
°
Reasonable rate of change with noncondensing relative humidity during the
transition from warm to cold
Relative humidity: 10% to 80%, noncondensing
Altitude: 0 to 40,000 feet (0 to 12,192 meters)
Cooling Airflow Direction
Each enclosure includes its own forced-air cooling fans or blowers. Air flow for each
enclosure enters from the front of the modular cabinet and rack and exhausts at the
rear.
Typical Acoustic Noise Emissions
70 dB(A) (sound pressure level at operator position)
Tested Electrostatic Immunity
Contact discharge: 8 KV
Air discharge: 20 KV