NonStop NS-Series Servers Site Preparation (H06.03+)
Specifications for NonStop S-Series I/O Enclosures
HP Integrity NonStop NS-Series Site Preparation Guide—527836-005
4-2
Electrical Requirements
For detailed information about NonStop S-Series I/O enclosures and their components,
refer to the NonStop S-Series Planning and Configuration Guide.
Electrical Requirements
AC Input
Power Plugs
NonStop S-Series I/O enclosures have two AC power input cables and use a wide
range of power plugs for various geographical locations. For a complete list of power
plugs and their part numbers, refer to the CSSI Web. You can find the link to the CSSI
Web in the left navigation bar of the NonStop Technical Library at:
http://techlibrary.cac.cpqcorp.net/ntl
Uninterruptible Power Supply (UPS)
No individual UPS is available or supported for NonStop S-Series I/O enclosures. If
your require UPS support, you must provide a site UPS.
Heat Output
A fully populated enclosure outputs 5456 Btu per hour.
Factor 100-120 V ac Operation 200-240 V ac Operation
Nominal voltage 100-120 V ac 200-240 V ac
Voltage range 85-132 V ac 170-264 V ac
Line frequency 50/60Hz nominal 50/60Hz nominal
Frequency ranges 47-53 Hz or 57-63 Hz 47-53 Hz or 57-63 Hz
Branch circuits Two 20 circuits per enclosure Two 10 circuits per enclosure
Nominal VA 600 VA per power cord (1200 VA
total)
600 VA per power cord (1200
VA total)
Heat output 1600 W (6456 Btu/h) 1600 W (6456 Btu/h)