International: 200 to 240 V AC PDU Power Cords
International: 200 to 240 V AC PDU Power Cords
For information about power cords for a 200 to 240 V AC input, single phase, 32A
RMS modular cabinet, refer to International 200 to 240 V AC input, Single phase, 32A
RMS Modular Cabinet on page 5-4.
Grounding
A safety ground/protective earth conductor is required for each AC service entrance to
the NonStop server equipment. This ground must comply with local codes and any
other applicable regulations
Branch Circuits and Circuit Breakers
Modular cabinets for the Integrity NonStop NS-series system contain two PDUs. Each
of the two PDUs requires a separate branch circuit of these ratings:
Branch circuit requirements vary by the input voltage and the local codes and
applicable regulations regarding maximum circuit and total distribution loading. Select
circuit breaker ratings according to local codes and any applicable regulations for the
circuit capacity.
Region Volts Amps
North America and Japan 208 24
North America and Japan 200 - 240 40
International 380 - 415 16
International 200 - 240 32
Caution. Be sure the hardware configuration and resultant power loads of each cabinet within
the system does not exceed the capacity of the branch circuit according to applicable electrical
codes and regulations.