NonStop NS1000 Planning Guide (H06.05+)
System Installation Specifications
HP Integrity NonStop NS1000 Planning Guide—542527-004
3-9
Nonoperating Temperature, Humidity, and Altitude
Nonoperating Temperature, Humidity, and Altitude
•
Temperature:
°
Up to 72-hour storage: - 40° to 150° F (-40° to 66° C)
°
Up to 6-month storage: -20° to 131° F (-29° to 55° C)
°
Reasonable rate of change with noncondensing relative humidity during the
transition from warm to cold
•
Relative humidity: 10% to 80%, noncondensing
•
Altitude: 0 to 40,000 feet (0 to 12,192 meters)
Cooling Airflow Direction
Each enclosure includes its own forced-air cooling fans or blowers. Air flow for each
enclosure enters from the front of the modular cabinet and rack and exhausts at the
rear.
Typical Acoustic Noise Emissions
•
70 dB(A) (sound pressure level at operator position)
Tested Electrostatic Immunity
•
Contact discharge: 8 KV
•
Air discharge: 20 KV
Calculating Specifications for Enclosure
Combinations
The example configuration in this subsection shows listed components installed in a
single modular (42U) HP modular cabinet. Cabinet weight includes the PDUs and their
associated wiring and receptacles.
Power and thermal calculations assume that each enclosure in the cabinet is fully
populated. The power and heat load is less when enclosures are not fully populated,
such as a Fibre Channel disk module with fewer disk drives.
Humidity 15% to 80%,
noncondensing
40% to 50%,
noncondensing
6%, noncondensing
Altitude
2
0 to 10,000 feet
(0 to 3,048 meters)
--
1. Operating and recommended ranges refer to the ambient air temperature and humidity measured 19.7 in.
(50 cm) from the front of the air intake cooling vents.
2. For each 1000 feet (305 m) increase in altitude above 10,000 feet (up to a maximum of 15,000 feet), subtract
1.5° F (0.83° C) from the upper limit of the operating and recommended temperature ranges.
Specification Operating Range
1
Recommended
Range
1
Maximum Rate of Change
per Hour (page 2 of 2)