NonStop NS1000 Planning Guide (H06.05+)

Modular System Hardware
HP Integrity NonStop NS1000 Planning Guide542527-004
5-4
Modular Cabinets
°
Zero-U" rack design
PDU input characteristics
°
200 to 240 V ac, single phase, 40A RMS, 3-wire
°
50/60Hz
°
Non-NEMA Locking CS8265C, 50A input plug
°
6.5 feet (2 m) attached power cord
PDU output characteristics
°
3 circuit-breaker-protected 20A load segments
°
36 AC receptacles per PDU (12 per segment) - IEC 320 C13 10A receptacle
type
°
3 AC receptacles per PDU (1 per segment) - IEC 320 C19 12A receptacle type
Includes front and rear doors
International 380 to 415 V AC input, 3-phase Wye, 16A RMS
Modular Cabinet
EIA standard 19-inch rack with 42U of rack space
Geography: International
Recommended for most configurations
Includes 2 power distribution units (PDU)
°
Zero-U" rack design
PDU input characteristics
°
380 to 415 V ac, 3-phase Wye, 16A RMS, 5-wire
°
50/60Hz
°
IEC309 5-pin, 16A input plug
°
6.5 feet (2 m) attached power cord
PDU output characteristics
°
3 circuit-breaker-protected 16A load segments
°
36 AC receptacles per PDU (12 per segment) - IEC 320 C13 10A receptacle
type
°
3 AC receptacles per PDU (1 per segment) - IEC 320 C19 12A receptacle type
Includes front and rear doors
International 200 to 240 V AC input, Single phase, 32A RMS
Modular Cabinet
EIA standard 19-inch rack with 42U of rack space
Geography: International
Recommended for most configurations
Includes 2 power distribution units (PDU)
°
Zero-U" rack design
PDU input characteristics
°
200 to 240 V ac, single phase, 32A RMS, 3-wire
°
50/60Hz
°
IEC309 3-pin, 32A input plug
°
6.5 feet (2 m) attached power cord
PDU output characteristics