NonStop NS1000 Planning Guide (H06.06+)

System Installation Specifications
HP Integrity NonStop NS1000 Planning Guide542527-002
3-5
Model R5500 XR Integrated UPS
Power and current specifications for each type of enclosure are:
Model R5500 XR Integrated UPS
For complete information and specifications, refer to the HP UPS R5500 XR Models
User Guide. This guide is available at:
http://h10032.www1.hp.com/ctg/Manual/c00065453.pdf
Enclosure Type
AC Power
Lines per
Enclosure
1
Apparent Power
(volt-amps
measured on
single AC line
with one line
powered)
Apparent Power
(volt-amps
measured on
single AC line
with both lines
powered)
5
Peak Inrush
Current
(amps)
Blade element
(rx2620):
4 GB memory
8 GB memory
2
2
220
240
Per line:
125
140
Total:
250
280
17
17
IOAM enclosure
2
4 420 250 500 68
Fibre Channel
disk module
3
2 220 140 280 14
Maintenance
switch (Ethernet)
4
150- 4
1
Half of the plugs for an enclosure must be connected to the left-side PDU and the other half connected to the
right-side PDU or extension bars (if the optional UPS is installed). PDUs must be supplied from separate branch
circuits.
2
Measured with 10 Fibre Channel ServerNet adapters installed and active.
3
Measured with 14 disk drives installed and active.
4
Maintenance switch has only one plug. If a UPS is installed in the modular cabinet, the maintenance switch
plug must be connected to the extension bars on the right-side of the modular cabinet.
5
Total apparent power is the sum of the two AC power lines feeding the enclosure. Electrical load is shared
equally between the two lines.
Version
Operating
Voltage Settings
Power Out
(VA/Watts) Input Plug Branch Circuit
North America
and Japan
200/208*, 220,
230, 240
5000/4500 L6-30P Dedicated 30 Amp
Other
International
200, 230*, 240 6000/5400 IEC-309 32
Amp
Dedicated 30 Amp
If 200/208 Then 5000/4500
* Factory-default setting