NonStop NS1000 Planning Guide (H06.06+)
Modular System Hardware
HP Integrity NonStop NS1000 Planning Guide—542527-002
5-5
Power Distribution Units (PDUs)
•
PDU output characteristics
°
3 circuit-breaker-protected 20A load segments
°
36 AC receptacles per PDU (12 per segment) - IEC 320 C13 10A receptacle
type
°
3 AC receptacles per PDU (1 per segment) - IEC 320 C19 12A receptacle type
•
Includes front and rear doors
Power Distribution Units (PDUs)
Two power distribution units (PDUs) are installed to provide redundant power outlets
for the components mounted in the modular cabinet. Each PDU is 60 inches long and
has 39 AC receptacles, three circuit breakers, and an AC power cord. The PDU is
oriented with the AC power cord exiting the modular cabinet at either the top or bottom
of the cabinet depending on the sites power feed needs.
For information about specific PDU input and output characteristics for PDUs factory-
installed in modular cabinets, refer to:
•
North America and Japan 208 V AC input, 3-phase delta, 24A RMS Modular
Cabinet on page 5-3
•
North America and Japan 200 to 240 V AC input, Single phase, 40A RMS Modular
Cabinet on page 5-3
•
International 380 to 415 V AC input, 3-phase Wye, 16A RMS Modular Cabinet on
page 5-4
•
International 200 to 240 V AC input, Single phase, 32A RMS Modular Cabinet on
page 5-4
Each PDU in a modular cabinet has:
•
36 AC receptacles per PDU (12 per segment) - IEC 320 C13 10A receptacle type
•
3 AC receptacles per PDU (1 per segment) - IEC 320 C19 12A receptacle type
•
3 circuit-breakers
These PDU options are available to receive power from the site AC power source:
•
208 V ac, three-phase delta for North America and Japan
•
200 to 240 V ac, single phase for North America and Japan
•
380 to 415 V ac three-phase wye for International
•
200 to 240 V ac single phase for international
Each PDU distributes the site AC power as single phase 200 to 240 V ac to the 39
outlets for connecting the power cords from the components mounted in the modular
cabinet. These outlets provide the 180-264 V ac required by the modular hardware.
Note. If your system includes the optional rackmounted HP R5500 XR UPS, the modular
cabinet will have one PDU located on the rear left side and four extension bars on the rear right
side.