Fault-Tolerant Configuration
Fault-Tolerant Configuration
You can configure the dedicated service LAN as described in the OSM Migration
Guide. HP recommends that you use a fault-tolerant LAN configuration. A fault-tolerant
configuration includes these connections to two maintenance switches:
Connect one system console to each maintenance switch.
Connect one of the two ServerNet switch boards in the IOAM enclosure to each
maintenance switch.
Connect one G4SA to each maintenance switch.
Connect one maintenance switch to an HP extension bar that is powered by the
UPS. HP extension bars are installed in place of a PDU on the rear right side of the
modular cabinet.
Caution. To avoid possible conflicts on the LAN:
If the configuration includes two maintenance switches, install and configure one switch
completely, including assigning its IP address, before you install the other.
Only one connection between the maintenance switches is permitted. More than one
connection overloads network traffic, rendering the dedicated service LAN unusable.
If ServerNet switch boards in the IOAM enclosure will have static IP addresses, configure
one completely, including assigning the IP address, before you configure the other.