NonStop NS1000 Planning Guide (H06.07+)
Control, Configuration, and Maintenance Tools
HP Integrity NonStop NS1000 Planning Guide—542527-003
B-8
Fault-Tolerant Configuration
Fault-Tolerant Configuration
You can configure the dedicated service LAN as described in the OSM Migration
Guide. HP recommends that you use a fault-tolerant LAN configuration. A fault-tolerant
configuration includes these connections to two maintenance switches:
•
Connect one system console to each maintenance switch.
•
Connect one of the two ServerNet switch boards in the IOAM enclosure to each
maintenance switch.
•
Connect one G4SA to each maintenance switch.
•
Connect one maintenance switch to an HP extension bar that is powered by the
UPS. HP extension bars are installed in place of a PDU on the rear right side of the
modular cabinet.
Caution. To avoid possible conflicts on the LAN:
•
If the configuration includes two maintenance switches, install and configure one switch
completely, including assigning its IP address, before you install the other.
•
Only one connection between the maintenance switches is permitted. More than one
connection overloads network traffic, rendering the dedicated service LAN unusable.
•
If ServerNet switch boards in the IOAM enclosure will have static IP addresses, configure
one completely, including assigning the IP address, before you configure the other.