NonStop NS1000 Planning Guide (H06.07+)
System Installation Specifications
HP Integrity NonStop NS1000 Planning Guide—542527-003
3-3
North America and Japan: 208 V AC PDU Power
North America and Japan: 208 V AC PDU Power
The PDU power characteristics are:
For additional information about the 208 V AC input, 3-phase delta, 24A RMS PDU
power option, refer to North America and Japan 208 V AC input, 3-phase delta, 24A
RMS Power on page 5-3.
North America and Japan: 200 to 240 V AC PDU Power
The PDU power characteristics are:
For additional information about the 200 to 240 V AC input, single phase, 40A RMS
PDU power option refer to North America and Japan 200 to 240 V AC input, Single
phase, 40A RMS Power on page 5-4.
PDU input
characteristics
•
208 V ac, 3-phase delta, 24A RMS, 4-wire
•
50/60Hz
•
NEMA L15-30 input plug
•
6.5 feet (2 m) attached power cord
PDU output
characteristics
•
3 circuit-breaker-protected 13.86A load segments
•
36 AC receptacles per PDU (12 per segment) - IEC 320 C13 10A
receptacle type
•
3 AC receptacles per PDU (1 per segment) - IEC 320 C19 12A
receptacle type
PDU input
characteristics
•
200 to 240 V ac, single phase, 40A RMS, 3-wire
•
50/60Hz
•
Non-NEMA Locking CS8265C, 50A input plug
•
6.5 feet (2 m) attached power cord
PDU output
characteristics
•
3 circuit-breaker-protected 20A load segments
•
36 AC receptacles per PDU (12 per segment) - IEC 320 C13 10A
receptacle type
•
3 AC receptacles per PDU (1 per segment) - IEC 320 C19 12A
receptacle type