NonStop NS1000 Planning Guide (H06.07+)
System Installation Specifications
HP Integrity NonStop NS1000 Planning Guide—542527-003
3-11
Environmental Specifications
Environmental Specifications
Heat Dissipation Specifications and Worksheet
Operating Temperature, Humidity, and Altitude
Topic Page
Heat Dissipation Specifications and Worksheet
3-11
Operating Temperature, Humidity, and Altitude 3-11
Nonoperating Temperature, Humidity, and Altitude 3-12
Cooling Airflow Direction 3-12
Typical Acoustic Noise Emissions 3-12
Tested Electrostatic Immunity 3-12
Enclosure Type
Number
Installed
Unit Heat
(Btu/hour
with single
AC line
powered)
Unit Heat
(Btu/hour
with both
AC lines
powered)
Total
(BTU/hour)
Blade element (rx2620):
4 GB memory
8 GB memory
751
819
853
956
IOAM
1
1504 1808
Fibre Channel disk module
2
990 1187
Maintenance switch (Ethernet)
3
300 -
Rackmount console system unit
Keyboard and display
696 -
1
Measured with 10 Fibre Channel ServerNet adapters installed and active.
2
Measured with 14 disk drives installed and active.
3
Maintenance switch has only one plug. If a UPS is installed in the modular cabinet, the maintenance switch
plug must be connected to the extension bars on the right-side of the modular cabinet.
Specification Operating Range
1
Recommended
Range
1
Maximum Rate of Change
per Hour (page 1 of 2)
Temperature (all
except Fibre
Channel disk
module)
41° to 95° F
(5° to 35° C)
68° to 72° F
(20° to 25° C)
9° F (5° C) Repetitive
36° F (20° C) Nonrepetitive
Temperature (Fibre
Channel disk
module)
50° to 95° F
(10° to 35° C)
-0.6° F (1° C) Repetitive
1.6° F (3° C) Nonrepetitive