NonStop NS1000 Planning Guide (H06.08+)
— “International 200 to 240 V AC input, Single phase, 32A RMS Power” (page 52)
— “Power Distribution Units (PDUs)” (page 52)
• Changed the C19 receptacle type from 12A to 16A in these sections:
— “North America and Japan: 208 V AC PDU Power” (page 26)
— “North America and Japan: 200 to 240 V AC PDU Power” (page 26)
— “International: 380 to 415 V AC PDU Power” (page 27)
— “International: 200 to 240 V AC PDU Power” (page 27)
— “North America and Japan 208 V AC input, 3-phase delta, 24A RMS Power” (page 51)
— “North America and Japan 200 to 240 V AC input, Single phase, 40A RMS Power”
(page 51)
— “International 380 to 415 V AC input, 3-phase Wye, 16A RMS Power” (page 51)
— “International 200 to 240 V AC input, Single phase, 32A RMS Power” (page 52)
— “Power Distribution Units (PDUs)” (page 52)
• Added new procedures to “AC Power Monitoring” (page 120), including the new subsections,
“How OSM Power Failure Support Works” (page 121), “Considerations for Ride-Through
Time Configuration” (page 121), and “Considerations for Site UPS Configurations” (page 122).
• Added note to “OSM” (page 119) indicating that HP Insight Remote Support Advanced
(Insight RSA) is the go-forward remote support solution for NonStop systems, replacing
the OSM Notification Director in both modem-based and HP Instant Support Enterprise
Edition (ISEE) remote support solutions.
New and Changed Information for 542527–009
• Corrected the operating temperatures under “Operating Temperature, Humidity, and
Altitude” (page 34) and “Nonoperating Temperature, Humidity, and Altitude” (page 34).
• Indicated under “Default Naming Conventions” (page 90) that changing the process names
for $ZTCP0 and $ZTCP1 will make some components inaccessible.
• Changed the weight of the PDU monitored configuration from 303 lbs. to 328 lbs. due to the
additional weight of the rack extension. See Table 3-1: Example of Cabinet Load Calculations
(page 36) and “Modular Cabinet and Enclosure Weights With Worksheet” (page 32).
• Changed VIO “IP Addresses” (page 115) from 192.231.36.222 to 192.231.36.202 and
192.231.36.223 to 192.231.36.203.
New and Changed Information for 542527–008
The following topics have been updated for this edition:
• “IP Addresses” (page 115) has been updated to describe the static IP addresses for Blade
iLOs.
• “One System Console Managing One System (Setup Configuration)” (page 110)
• “Primary and Backup System Consoles Managing One System ” (page 111)
Document Organization
ContentsSection
This chapter provides an overview of the modular
Integrity NonStop NS1000 system.
Chapter 1 (page 15)
This chapter outlines topics to consider when planning
or upgrading the installation site.
Chapter 2 (page 19)
This chapter provides the installation specifications for a
fully populated Integrity NonStop NS1000 enclosure.
Chapter 3 (page 25)
10