NOTE: If your system includes the optional rackmounted HP R5500 XR UPS, the modular
cabinet will have one PDU located on the rear left side and four extension bars on the rear right
side. To provide redundancy, components are plugged into the left-side PDU and the extension
bars. Each extension bar is plugged into the UPS.
“Example of a 4-Processor Configuration” (page 35), has four processors (one in each blade
element), two VIO enclosures, and two Fibre Channel disk modules installed in a 42U modular
cabinet. The weight, power, and thermal calculations for the cabinet and installed components
are shown in “Example of a 4-Processor Configuration” (page 35). For a total thermal load for
a system with multiple cabinets, add the heat outputs for all the cabinets in the system.
Figure 3-1 Example of a 4-Processor Configuration
Calculating Specifications for Enclosure Combinations 35