NonStop NS1000 Planning Guide (H06.08+)

IEC309 5-pin, 16A input plug
6.5 feet (2 m) attached power cord
PDU output characteristics
3 circuit-breaker-protected 16A load segments
36 AC receptacles per PDU (12 per segment) - IEC 320 C13 12A receptacle type
3 AC receptacles per PDU (1 per segment) - IEC 320 C19 16A receptacle type
Includes front and rear doors
International 200 to 240 V AC input, Single phase, 32A RMS Power
EIA standard 19-inch rack with 36 or 42 U of rack space
Geography: International
Recommended for most configurations
Harmonized power cord
Includes 2 power distribution units (PDU)
Zero-U rack design
PDU input characteristics
200 to 240 V ac, single phase, 32A RMS, 3-wire
50/60Hz
IEC309 3-pin, 32A input plug
6.5 feet (2 m) attached power cord
PDU output characteristics
3 circuit-breaker-protected 20A load segments
36 AC receptacles per PDU (12 per segment) - IEC 320 C13 12A receptacle type
3 AC receptacles per PDU (1 per segment) - IEC 320 C19 16A receptacle type
Includes front and rear doors
Power Distribution Units (PDUs)
Two power distribution units (PDUs) are installed to provide redundant power outlets for the
components mounted in the modular cabinet. The PDUs are oriented inward, facing the
components within the rack. Each PDU is 60 inches long and has 39 AC receptacles, three circuit
breakers, and an AC power cord. The PDU is oriented with the AC power cord exiting the
modular cabinet at either the top or bottom rear corners of the cabinet, depending on the sites
power feed needs.
NOTE: If your system includes the optional rackmounted HP R5500 XR UPS, the modular
cabinet will have one PDU located on the rear left side and four extension bars on the rear right
side. To provide redundancy, components are plugged into the left-side PDU and the extension
bars. Each extension bar is plugged into the UPS.
For information about specific PDU input and output characteristics for PDUs factory-installed
in modular cabinets, refer to:
“North America and Japan 208 V AC input, 3-phase delta, 24A RMS Power” (page 51)
“North America and Japan 200 to 240 V AC input, Single phase, 40A RMS Power (page 51)
“International 380 to 415 V AC input, 3-phase Wye, 16A RMS Power” (page 51)
“International 200 to 240 V AC input, Single phase, 32A RMS Power” (page 52)
52 Modular System Hardware