NonStop NS1200 Planning Guide

Power can enter the Integrity NonStop NS1200 server from either the top or the bottom rear of
the modular cabinets, depending on how the cabinets are ordered from HP and the AC power
feeds are routed at the site. Integrity NonStop NS1200 server cabinets can be ordered with the
AC power cords for the PDU installed either:
Top: Power and I/O cables are routed from above the modular cabinet.
Bottom: Power and I/O cables are routed from below the modular cabinet
NOTE: If your system includes the optional rackmounted HP R5500 XR UPS, the modular
cabinet will have one PDU located on the rear left side and four extension bars on the rear
right side. To provide redundancy, components are plugged into the left-side PDU and the
extension bars. Each extension bar is plugged into the UPS. The R5500 XR UPS AC input
power cord is routed as described above, and the large output receptacle is unused.
For information on the modular cabinets, refer to “Modular Cabinets” (page 37). For information
on the PDUs, refer to “Power Distribution Units (PDUs)” (page 37).
North America and Japan: 208 V AC PDU Power
The cabinet includes two power distribution units (PDU). The PDU power characteristics are:
208 V ac, 3-phase delta, 24A RMS, 4-wire
50/60Hz
NEMA L15-30 input plug
6.5 feet (2 m) attached power cord
PDU input characteristics
3 circuit-breaker-protected 13.86A load segments
36 AC receptacles per PDU (12 per segment) - IEC 320
C13 12A receptacle type
3 AC receptacles per PDU (1 per segment) - IEC 320
C19 16A receptacle type
PDU output characteristics
North America and Japan: 200 to 240 V AC PDU Power
The cabinet includes two power distribution units (PDU). The PDU power characteristics are:
200 to 240 V ac, single phase, 40A RMS, 3-wire
50/60Hz
Non-NEMA Locking CS8265C, 50A input plug
6.5 feet (2 m) attached power cord
PDU input characteristics
3 circuit-breaker-protected 20A load segments
36 AC receptacles per PDU (12 per segment) - IEC 320
C13 12A receptacle type
3 AC receptacles per PDU (1 per segment) - IEC 320
C19 16A receptacle type
PDU output characteristics
AC Input Power for Modular Cabinets 41