NonStop NS14000 Planning Guide (H06.10+)

NOTE: If your system includes the optional rackmounted HP R5500 XR UPS, the modular
cabinet will have one PDU located on the rear left side and four extension bars on the rear
right side. To provide redundancy, components are plugged into the left-side PDU and the
extension bars. Each extension bar is plugged into the UPS. The R5500 XR UPS AC input
power cord is routed as described above, and the large output receptacle is unused.
For information on the modular cabinets, refer to “Modular Cabinets” (page 50). For information
on the PDUs, refer to “Power Distribution Units (PDUs)” (page 52).
North America and Japan: 208 V AC PDU Power
The PDU power characteristics are:
208 V ac, 3-phase delta, 24A RMS, 4-wire
50/60Hz
NEMA L15-30 input plug
6.5 feet (2 m) attached power cord
PDU input characteristics
3 circuit-breaker-protected 13.86A load segments
36 AC receptacles per PDU (12 per segment) - IEC 320
C13 10A receptacle type
3 AC receptacles per PDU (1 per segment) - IEC 320
C19 12A receptacle type
PDU output characteristics
For additional information, refer to “North America and Japan 208 V AC input, 3-phase delta,
24A RMS Power” (page 51).
North America and Japan: 200 to 240 V AC PDU Power
The PDU power characteristics are:
200 to 240 V ac, single phase, 40A RMS, 3-wire
50/60Hz
Non-NEMA Locking CS8265C, 50A input plug
6.5 feet (2 m) attached power cord
PDU input characteristics
3 circuit-breaker-protected 20A load segments
36 AC receptacles per PDU (12 per segment) - IEC 320
C13 10A receptacle type
3 AC receptacles per PDU (1 per segment) - IEC 320
C19 12A receptacle type
PDU output characteristics
For additional information, refer to “North America and Japan 200 to 240 V AC input, Single
phase, 40A RMS Power” (page 51).
24 System Installation Specifications