NonStop NS14000 Planning Guide (H06.10+)

International: 380 to 415 V AC PDU Power
The PDU power characteristics are:
380 to 415 V ac, 3-phase Wye, 16A RMS, 5-wire
50/60Hz
IEC309 5-pin, 16A input plug
6.5 feet (2 m) attached harmonized power cord
PDU input characteristics
3 circuit-breaker-protected 16A load segments
36 AC receptacles per PDU (12 per segment) - IEC 320
C13 10A receptacle type
3 AC receptacles per PDU (1 per segment) - IEC 320
C19 12A receptacle type
PDU output characteristics
For additional information, refer to “International 380 to 415 V AC input, 3-phase Wye, 16A RMS
Power” (page 51).
International: 200 to 240 V AC PDU Power
The PDU power characteristics are:
200 to 240 V ac, single phase, 32A RMS, 3-wire
50/60Hz
IEC309 3-pin, 32A input plug
6.5 feet (2 m) attached harmonized power cord
PDU input characteristics
3 circuit-breaker-protected 20A load segments
36 AC receptacles per PDU (12 per segment) - IEC 320
C13 10A receptacle type
3 AC receptacles per PDU (1 per segment) - IEC 320
C19 12A receptacle type
PDU output characteristics
For additional information, refer to “International 200 to 240 V AC input, Single phase, 32A RMS
Power” (page 52).
Grounding
A safety ground/protective earth conductor is required for each AC service entrance to the
NonStop server equipment. This ground must comply with local codes and any other applicable
regulations
Branch Circuits and Circuit Breakers
Modular cabinets for the Integrity NonStop NS14000 system contain two PDUs. Each of the two
PDUs requires a separate branch circuit of these ratings:
AmpsVoltsRegion
24208North America and Japan
40200 - 240North America and Japan
16380 - 415International
32200 - 240International
AC Input Power for Modular Cabinets 25