NonStop NS14000 Planning Guide (H06.10+)

NOTE: If your system includes the optional rackmounted HP R5500 XR UPS, the modular
cabinet will have one PDU located on the rear left side and four extension bars on the rear right
side. To provide redundancy, components are plugged into the left-side PDU and the extension
bars. Each extension bar is plugged into the UPS.
Power and current specifications for each type of enclosure are:
Peak Inrush
Current (amps)
Apparent Power
(volt-amps
measured on
single AC line
with both lines
powered)5
Apparent Power
(volt-amps
measured on
single AC line with
one line powered)
AC Power Lines
per Enclosure1
Enclosure Type
17
17
Total:
760
780
Per line:
380
390
680
710
2
2
4-processor
NonStop Blade
Element: 16 GB
memory boards
32 GB memory
boards
672201101502LSU (with four
LSUs)
303261632622VIO enclosure2
143481742902Fibre Channel
disk module3
4--441Maintenance
switch
(Ethernet)4
1 Half of the plugs for an enclosure must be connected to the left-side PDU and the other half connected to the
right-side PDU or extension bars (if the optional UPS is installed). PDUs must be supplied from separate branch
circuits.
2 Measured with PICs installed in slots 1, 2, 5, 6a/7a, 7b, and 7c; PIC in slot 7c had two external connections. Sysex
was running. Fans were running at full speed.
3 Measured with 14 disk drives installed and active.
4 Maintenance switch has only one plug. If a UPS is installed in the modular cabinet, the maintenance switch plug
must be connected to the extension bars on the right side of the modular cabinet.
5 Total apparent power is the sum of the two AC power lines feeding the enclosure. Electrical load is shared equally
between the two lines.
Model R5500 XR Integrated UPS
Branch CircuitInput PlugPower Out (VA/Watts)Operating Voltage
Settings
Version
Dedicated 30 AmpL6-30P5000/4500200/208
1
, 220, 230, 240North America and
Japan
Dedicated 30 AmpIEC-309 32 Amp6000/5400200, 230
1
, 240Other International
Then 5000/4500If 200/208
1 Factory-default setting
For complete information and specifications, refer to the HP UPS R5500 XR Models User Guide.
This guide is available at:
http://h10032.www1.hp.com/ctg/Manual/c00065453.pdf
AC Input Power for Modular Cabinets 27