NonStop NS14000 Planning Guide (H06.10+)

Heat Dissipation Specifications and Worksheet
Total (BTU/hour)Unit Heat (Btu/hour
with both AC lines
powered)
Unit Heat (Btu/hour
with single AC line
powered)
Number InstalledEnclosureType
2594
2662
2320
2423
4-processor NonStop
Blade Element:
16 GB memory boards
32 GB memory boards
750512LSU (with four LSUs)
1112893VIO enclosure1
1187990Fibre Channel disk
module2
-150Maintenance switch
(Ethernet)3
-696Rackmount console
system unit with
keyboard and display
1 Measured with PICs installed in slots 1, 2, 5, 6a/7a, 7b, and 7c; PIC in slot 7c had two external connections. Sysex
was running. Fans were running at full speed.
2 Measured with 14 disk drives installed and active.
3 Maintenance switch has only one plug. If a UPS is installed in the modular cabinet, the maintenance switch plug
must be connected to the extension bars on the right side of the modular cabinet.
Operating Temperature, Humidity, and Altitude
Maximum Rate of Change
per Hour
Recommended Range1Operating Range1Specification
9° F (5° C) Repetitive 36° F
(20° C) Nonrepetitive
68° to 72° F (20° to 25° C)41° to 95° F (5° to 35° C)Temperature (all except
Fibre Channel disk module)
0.6° F (1° C) Repetitive 1.6°
F (3° C) Nonrepetitive
-50° to 95° F (10° to 35° C)Temperature (Fibre Channel
disk module)
6%, noncondensing40% to 50%, noncondensing15% to 80%, noncondensingHumidity
--0 to 10,000 feet (0 to 3,048
meters)
Altitude2
1. Operating and recommended ranges refer to the ambient air temperature and humidity measured 19.7 in. (50 cm)
from the front of the air intake cooling vents.
2. For each 1000 feet (305 m) increase in altitude above 10,000 feet (up to a maximum of 15,000 feet), subtract 1.5° F
(0.83° C) from the upper limit of the operating and recommended temperature ranges.
Nonoperating Temperature, Humidity, and Altitude
Temperature:
Up to 72-hour storage: - 40° to 150° F (-40° to 66° C)
Up to 6-month storage: -20° to 131° F (-29° to 55° C)
Reasonable rate of change with noncondensing relative humidity during the transition
from warm to cold
Relative humidity: 10% to 80%, noncondensing
Altitude: 0 to 40,000 feet (0 to 12,192 meters)
Environmental Specifications 31