NonStop NS14000 Planning Guide (H06.10+)

NOTE: If your system includes the optional rackmounted HP R5500 XR UPS, the modular
cabinet will have one PDU located on the rear left side and four extension bars on the rear right
side. To provide redundancy, components are plugged into the left-side PDU and the extension
bars. Each extension bar is plugged into the UPS.
North America and Japan 208 V AC input, 3-phase delta, 24A RMS Power
EIA standard 19-inch rack with 42U of rack space
Geography: North America and Japan
Recommended for most configurations
Includes 2 power distribution units (PDU): Zero-U rack design
PDU input characteristics
208 V ac, 3-phase delta, 24A RMS, 4-wire
50/60Hz
NEMA L15-30 input plug
6.5 feet (2 m) attached power cord
PDU output characteristics
3 circuit-breaker-protected 13.86A load segments
36 AC receptacles per PDU (12 per segment) - IEC 320 C13 10A receptacle type
3 AC receptacles per PDU (1 per segment) - IEC 320 C19 12A receptacle type
Includes front and rear doors
North America and Japan 200 to 240 V AC input, Single phase, 40A RMS Power
EIA standard 19-inch rack with 42U of rack space
Geography: North America and Japan
Recommended for most configurations
Includes 2 power distribution units (PDU): Zero-U rack design
PDU input characteristics
200 to 240 V ac, single phase, 40A RMS, 3-wire
50/60Hz
Non-NEMA Locking CS8265C, 50A input plug
6.5 feet (2 m) attached power cord
PDU output characteristics
3 circuit-breaker-protected 20A load segments
36 AC receptacles per PDU (12 per segment) - IEC 320 C13 10A receptacle type
3 AC receptacles per PDU (1 per segment) - IEC 320 C19 12A receptacle type
Includes front and rear doors
International 380 to 415 V AC input, 3-phase Wye, 16A RMS Power
EIA standard 19-inch rack with 42U of rack space
Geography: International
Recommended for most configurations
Harmonized power cord
Includes 2 power distribution units (PDU): Zero-U rack design
PDU input characteristics
380 to 415 V ac, 3-phase Wye, 16A RMS, 5-wire
50/60Hz
Modular Hardware Components 51