NonStop NS14000 Planning Guide (H06.10+)

IEC309 5-pin, 16A input plug
6.5 feet (2 m) attached power cord
PDU output characteristics
3 circuit-breaker-protected 16A load segments
36 AC receptacles per PDU (12 per segment) - IEC 320 C13 10A receptacle type
3 AC receptacles per PDU (1 per segment) - IEC 320 C19 12A receptacle type
Includes front and rear doors
International 200 to 240 V AC input, Single phase, 32A RMS Power
EIA standard 19-inch rack with 42U of rack space
Geography: International
Recommended for most configurations
Harmonized power cord
Includes 2 power distribution units (PDU): Zero-U rack design
PDU input characteristics
200 to 240 V ac, single phase, 32A RMS, 3-wire
50/60Hz
IEC309 3-pin, 32A input plug
6.5 feet (2 m) attached power cord
PDU output characteristics
3 circuit-breaker-protected 20A load segments
36 AC receptacles per PDU (12 per segment) - IEC 320 C13 10A receptacle type
3 AC receptacles per PDU (1 per segment) - IEC 320 C19 12A receptacle type
Includes front and rear doors
Power Distribution Units (PDUs)
Two power distribution units (PDUs) are installed to provide redundant power outlets for the
components mounted in the modular cabinet. The PDUs are oriented inward, facing the
components within the modular cabinet. Each PDU is 60 inches long and has 39 AC receptacles,
three circuit breakers, and an AC power cord. The PDU is oriented with the AC power cord
exiting the modular cabinet at either the top or bottom rear corners of the cabinet, depending on
the sites power feed needs.
NOTE: If your system includes the optional rackmounted HP R5500 XR UPS, the modular
cabinet will have one PDU located on the rear left side and four extension bars on the rear right
side. To provide redundancy, components are plugged into the left-side PDU and the extension
bars. Each extension bar is plugged into the UPS.
Each PDU in a modular cabinet has:
36 AC receptacles per PDU (12 per segment) - IEC 320 C13 10A receptacle type
3 AC receptacles per PDU (1 per segment) - IEC 320 C19 12A receptacle type
3 circuit-breakers
These PDU options are available to receive power from the site AC power source:
208 V ac, three-phase delta for North America and Japan
200 to 240 V ac, single phase for North America and Japan
380 to 415 V ac three-phase wye for International
200 to 240 V ac single phase for international
52 Modular System Hardware