NonStop NS14000 Series Planning Guide (H06.13+)
Each single-phase PDU in a modular cabinet has:
• 36 AC receptacles per PDU (12 per segment) - IEC 320 C13 12A receptacle type
• 3 AC receptacles per PDU (1 per segment) - IEC 320 C19 16A receptacle type
• 3 circuit-breakers
These PDU options are available to receive power from the site AC power source:
• 200 to 240 V AC, single-phase for North America and Japan
• 200 to 240 V AC single-phase for International
Each PDU distributes the site AC power as single phase 200 to 240 V AC to the 39 outlets for
connecting the power cords from the components mounted in the modular cabinet.
AC Power Feeds, Monitored Single-Phase PDUs
Power can enter the NonStop NS14000 series server from either the top or the bottom rear of the
modular cabinets, depending on how the cabinets are ordered from HP and the AC power feeds
are routed at the site. NonStop NS14000 series server cabinets can be ordered with the AC power
cords for the PDU installed either:
• Top: Power and I/O cables are routed from above the modular cabinet.
• Bottom: Power and I/O cables are routed from below the modular cabinet
For information on the modular cabinets, refer to “Modular Cabinets” (page 41).
The AC power feed cables for the PDUs are mounted to exit the modular cabinet at either the top
or bottom rear corners of the cabinet depending on what is ordered for the site power feed.
Top AC Power Feed, Monitored Single-Phase PDUs
Figure 2 shows the AC power feed cables on PDUs for AC feed at the top of the cabinet:
Figure 2 Top AC Power Feed, Monitored Single-Phase PDUs
42 System Installation Specifications