NonStop NS14000 Series Planning Guide (H06.13+)
Figure 5 Bottom AC Power Feed When Optional UPS and ERM are Installed
Input and Output Power Characteristics, Monitored Single-Phase PDUs
The cabinet includes two monitored single-phase PDUs.
North America and Japan: 200 to 240 V AC, Monitored Single-Phase PDUs
The North America and Japan PDU power characteristics are:
PDU input characteristics
• 200 to 240 V AC, single phase, 40A RMS, 3-wire
• 50/60Hz
• Non-NEMA Locking CS8265C, 50A input plug
• 6.5 feet (2 m) attached power cord
PDU output characteristics
• 3 circuit-breaker-protected 20A load segments
• 36 AC receptacles per PDU (12 per segment) - IEC 320
C13 12A receptacle type
• 3 AC receptacles per PDU (1 per segment) - IEC 320
C19 16A receptacle type
Monitored Single-Phase PDUs 45










