NonStop NS14000 Series Planning Guide (H06.13+)
International: 380 to 415 V AC, Monitored Three-Phase PDUs
The international PDU power characteristics are:
PDU input characteristics
• 380 to 415 V AC, 3-phase Wye, 16A RMS, 5-wire
• 50/60Hz
• IEC309 5-pin, 16A input plug
• 6.5 feet (2 m) attached harmonized power cord
PDU output characteristics
• 3 circuit-breaker-protected 16A load segments
• 36 AC receptacles per PDU (12 per segment) - IEC 320
C13 12A receptacle type
• 3 AC receptacles per PDU (1 per segment) - IEC 320
C19 16A receptacle type
Branch Circuits and Circuit Breakers, Monitored Three-Phase PDUs
Modular cabinets for the NonStop NS14000 series system that use a three-phase power
configuration with monitored three-phase PDUs contain two PDUs. In cabinets without the optional
rack-mounted UPS, each of the two PDUs requires a separate branch circuit of these ratings:
Amps (see following “CAUTION”)Volts (Phase-to-Phase)Region
30200 to 240North America and Japan
16
1
380 to 415International
1
Category D circuit breaker is required.
CAUTION: Be sure the hardware configuration and resultant power loads of each cabinet within
the system do not exceed the capacity of the branch circuit according to applicable electrical codes
and regulations.
NOTE: If your system includes the optional rackmounted HP R5500 XR UPS, the modular cabinet
will have one PDU located on the rear left side and four extension bars on the rear right side. To
provide redundancy, components are plugged into the left-side PDU and the extension bars. Each
extension bar is plugged into the UPS.
Branch circuit requirements vary by the input voltage and the local codes and applicable regulations
regarding maximum circuit and total distribution loading. Select circuit breaker ratings according
to local codes and any applicable regulations for the circuit capacity.
Select circuit breaker ratings according to local codes and any applicable regulations for the circuit
capacity. Note that circuit breaker ratings vary if your system includes the optional rackmounted
HP R5500 XR Integrated UPS.
Modular Three-Phase PDUs
Two three-phase modular power distribution units (PDUs) are installed to provide redundant power
outlets for the components mounted in the modular cabinet. Each 1U rack-mounted modular PDU
comes with four modular PDU extension bars. The PDUs are oriented facing each other within the
rack. Each PDU has 28 AC receptacles, six circuit breakers, and an AC power cord. The PDU is
oriented with the AC power cord exiting the modular cabinet at either the top or bottom rear
corners of the cabinet, depending on the site's power feed needs.
Modular Three-Phase PDUs 51