NonStop NS14000 Series Planning Guide (H06.13+)
Figure 13 Bottom AC Power Feed When Optional UPS and ERM are Installed
Input and Output Power Characteristics, Modular Three-Phase PDUs
The cabinet includes two modular three-phase PDUs.
North America and Japan: 200 to 240 V AC, Modular Three-Phase PDUs and Extension Bars
The North America and Japan PDU power characteristics are:
PDU input characteristics
• 200 to 240 V AC, 3-phase delta, 30A, 4-wire
• 50/60Hz
• NEMA L15-30 input plug
• 12 feet (3.6 m) attached power cord
6 IEC 320 C19 receptacles per PDU with 20A
circuit-breaker labels (L1, L2, L3, L4, L5, and L6)
PDU output characteristics
Extension bar input characteristics
• 200V to 240 V AC, 3-phase delta, 16A RMS, 4-wire
• 50/60Hz
• IEC 320–C20 input plug
• 6.5 feet (2.0 m) attached power cord
7 IEC 320 C13 receptacles per PDU with 12A maximum
per outlet
Extension bar output characteristics
56 System Installation Specifications