NonStop NS14000 Series Planning Guide (H06.13+)

Circuit Breaker Ratings for UPS
These ratings apply to systems with the optional rack-mounted HP R5000 UPS Integrated UPS that
is used for a single-phase power configuration:
UPS Input Rating
1
Input PlugPower Out
(VA/Watts)
Operating Voltage
Settings
Version
Dedicated 30 AmpL6-30P5000/4500200/208
2
,
220/230/240
North America and
Japan
Dedicated 30 AmpIEC 60309–32 Amp5000/4500200/208/220/230
3
,
240
International
Then 5000/4500If set at 200/208
1
The UPS input requires a dedicated (unshared) branch circuit that is suitably rated for your specific UPS.
2
Factory-default setting
3
Factory-default setting
For further information and specifications on the HP R5000 UPS, refer to the HP R5000 UPS User
Guide. This guide is available at http://bizsupport.austin.hp.com/bc/docs/support/
SupportManual/c00065453/c00065453.pdf
These ratings apply to systems with the optional rack-mounted HP R5500 XR Integrated UPS that
is used for a single-phase power configuration:
UPS Input Rating
1
Input PlugPower Out
(VA/Watts)
Operating Voltage
Settings
Version
Dedicated 30 AmpL6-30P5000/4500200/208
2
, 220,
230, 240
North America and
Japan
Dedicated 30 AmpIEC-309 32 Amp5000/4500200, 230
3
, 240International
Then 5000/4500If set at 200/208
1
The UPS input requires a dedicated (unshared) branch circuit that is suitably rated for your specific UPS.
2
Factory-default setting
3
Factory-default setting
For further information and specifications on the R5500 XR UPS, refer to the HP R5500 UPS User
Guide. This guide is available at:
http://bizsupport.austin.hp.com/bc/docs/support/SupportManual/c00065453/c00065453.pdf
PDU Strapping Configurations
PDUs are available in four static strapping configurations that are factory-installed in a modular
cabinet. The specific PDU strapping configuration for a particular site depends on the type and
voltage of AC power at the intended installation site for the system.
Grounding
A safety ground/protective earth conductor is required for each AC service entrance to the NonStop
server equipment. This ground must comply with local codes and any other applicable regulations.
58 System Installation Specifications