NonStop NS16000 Planning Guide (H06.08+)

System Configuration Guidelines
HP Integrity NonStop NS16000 Planning Guide529567-009
6-17
P-Switch to NonStop S-Series I/O Enclosure Cabling
This illustration shows the cables from the NonStop S-series IOMF 2 CRUs connected
to port 1 of the PICs in slot 4 of the X and Y p-switch, assigning the group number of
11:
These restrictions or requirements apply when integrating NonStop S-series I/O
enclosures into an Integrity NonStop NS16000 system:
Only NonStop S-series I/O enclosures equipped with IOMF 2 CRUs can be
connected to an Integrity NonStop NS16000 system. The IOMF 2 CRU must have
an MMF PIC installed.
NonStop S-series system enclosures can be converted to NonStop S-series I/O
enclosures, replacing the two PMF CRUs in each enclosure with IOMF 2 CRUs.
See the conversion instructions in the Hardware Service and Maintenance
Publications category of the Support and Service Library of NTL. See Support and
Service Library on page C-1.
P-Switch
X Fabric
P-Switch
Y Fabric
VST767.vsd
NonStop S-Series
I/O Enclosure
Integrity NonStop
NS-Series System
Fiber-Optic
ServerNet Cables
P-Switch
ServerNet I/O
PICs
Power-On
Cables