NonStop NS16000 Planning Guide (H06.08+)

Modular System Hardware
HP Integrity NonStop NS16000 Planning Guide529567-009
5-6
Power Distribution Units (PDUs)
Each PDU in a modular cabinet has:
36 AC receptacles per PDU (12 per segment) - IEC 320 C13 10A receptacle type
3 AC receptacles per PDU (1 per segment) - IEC 320 C19 12A receptacle type
3 circuit-breakers
These PDU options are available to receive power from the site AC power source:
208 V ac, three-phase delta for North America and Japan
200 to 240 V ac, single phase for North America and Japan
380 to 415 V ac three-phase wye for International
200 to 240 V ac single phase for international
Each PDU distributes the site AC power as single phase 200 to 240 V ac to the 39
outlets for connecting the power cords from the components mounted in the modular
cabinet. These outlets provide the 180-264 V ac required by the modular hardware.
The AC power feed cables for the PDUs are mounted to exit the modular cabinet at
either the top or bottom rear corners of the cabinet depending on what is ordered for
the site power feed.
This illustration shows the AC power feed cables on PDUs for AC feed at the bottom of
the cabinet and the AC power outlets along the PDU. These power outlets face in
toward the cabinet: