NonStop NS16000 Series Planning Guide (H06.11+)

Select circuit breaker ratings according to local codes and any applicable regulations for the circuit
capacity. Note that circuit breaker ratings vary if your system includes the optional rackmounted
HP R5000 UPS.
Circuit Breaker Ratings for UPS
These ratings apply to systems with the optional rack-mounted HP R5000 UPS Integrated UPS that
is used for a single-phase power configuration:
UPS Input Rating
1
Input PlugPower Out
(VA/Watts)
Operating Voltage
Settings
Version
Dedicated 30 AmpL6-30P5000/4500200/208
2
/220/230/240North America and
Japan
Dedicated 32 AmpIEC 60309–32A5000/4500200/208/220/230
2
/240International
1
The UPS input requires a dedicated (unshared) branch circuit that is suitably rated for your specific UPS.
2
Factory-default setting
For further information and specifications on the R5000 UPS, refer to the HP UPS R5000 User
Guide.
These ratings apply to systems with the optional rack-mounted HP R5500 XR Integrated UPS that
is used for a single-phase power configuration:
UPS Input Rating
1
Input PlugPower Out
(VA/Watts)
Operating Voltage
Settings
Version
Dedicated 30 AmpFor R5500 XR UPS:
L6-30P
5000/4500200/208
2
, 220,
230, 240
North America and
Japan
Dedicated 30 AmpFor R5500 XR UPS:
IEC-309 32 Amp
6000/5400200, 230
2
, 240International
Then 5000/4500If set at 200/208
1
The UPS input requires a dedicated (unshared) branch circuit that is suitably rated for your specific UPS.
2
Factory-default setting
For further information and specifications on the R5500 XR UPS, refer to the HP R5500 UPS User
Guide.
PDU Strapping Configurations
PDUs are available in four static strapping configurations that are factory-installed in a modular
cabinet. The specific PDU strapping configuration for a particular site depends on the type and
voltage of AC power at the intended installation site for the system.
Grounding
A safety ground/protective earth conductor is required for each AC service entrance to the NonStop
server equipment. This ground must comply with local codes and any other applicable regulations
Enclosure AC Input
Enclosures (NonStop Blade Element, processor switch, IOAM, and so forth) require:
ValueSpecification
200/208/220/230/240 V AC RMSNominal input voltage
180-264 V ACVoltage range
1
54 System Installation Specifications