NonStop NS16000 Series Planning Guide (H06.11+)

Peak Inrush Current
(amps)
Maximum Power
Consumption (VA)
Typical Power
Consumption (VA)
AC Power Lines per
Enclosure
1
Enclosure Type
51801252
MSA70 SAS disk
enclosure (empty)
5125752
D2700 SAS disk
enclosure (empty)
-95-
SAS 2.5 in., 10k rpm
disk drive
-74-
SAS 2.5 in., 15k rpm
disk drive
1.5 (5V current)66-SAS SSD
1.0 (12V current)
685305304IOAM enclosure
4
141101102Fibre Channel disk
module (no disk)
-1717-Fibre Channel disk
drive
420201Maintenance switch
(Ethernet)
5
-1761761Rack-mounted system
console system
(NSCR4)
21151051Rack-mounted system
console system
(NSCR110)
428281Rack-mounted console
system unit keyboard
and monitor
1
Half of the plugs for an enclosure must be connected to the left-side PDU and the other half connected to the right-side
PDU or extension bars (if the optional UPS is installed). PDUs must be supplied from separate branch circuits.
2
Measured with four LSU optical adapters installed and active. Each LSU logic board consumes 55 W.
3
Measured with three PICs installed and active. Each MMF PIC or SMF PIC consumes 13 W.
4
Measured with 10 Fibre Channel ServerNet adapters installed and active. Each FCSA or G4SA consumes 30 W.
5
Maintenance switch has only one plug. If a UPS is installed in the modular cabinet, the maintenance switch plug must
be connected to the extension bars on the right-side of the modular cabinet.
Dimensions and Weights
This subsection provides information about the dimensions and weights for modular cabinets and
enclosures installed in a modular cabinet and covers these topics:
“Service Clearances for the Modular Cabinet” (page 57)
“Unit Sizes” (page 57)
“Modular Cabinet Physical Specifications” (page 58)
“Enclosure Dimensions” (page 58)
“Modular Cabinet and Enclosure Weights With Worksheet” (page 59)
56 System Installation Specifications