NonStop NS16000 Series Planning Guide (H06.11+)
Peak Inrush Current
(amps)
Maximum Power
Consumption (VA)
Typical Power
Consumption (VA)
AC Power Lines per
Enclosure
1
Enclosure Type
51801252
MSA70 SAS disk
enclosure (empty)
5125752
D2700 SAS disk
enclosure (empty)
-95-
SAS 2.5 in., 10k rpm
disk drive
-74-
SAS 2.5 in., 15k rpm
disk drive
1.5 (5V current)66-SAS SSD
1.0 (12V current)
685305304IOAM enclosure
4
141101102Fibre Channel disk
module (no disk)
-1717-Fibre Channel disk
drive
420201Maintenance switch
(Ethernet)
5
-1761761Rack-mounted system
console system
(NSCR4)
21151051Rack-mounted system
console system
(NSCR110)
428281Rack-mounted console
system unit keyboard
and monitor
1
Half of the plugs for an enclosure must be connected to the left-side PDU and the other half connected to the right-side
PDU or extension bars (if the optional UPS is installed). PDUs must be supplied from separate branch circuits.
2
Measured with four LSU optical adapters installed and active. Each LSU logic board consumes 55 W.
3
Measured with three PICs installed and active. Each MMF PIC or SMF PIC consumes 13 W.
4
Measured with 10 Fibre Channel ServerNet adapters installed and active. Each FCSA or G4SA consumes 30 W.
5
Maintenance switch has only one plug. If a UPS is installed in the modular cabinet, the maintenance switch plug must
be connected to the extension bars on the right-side of the modular cabinet.
Dimensions and Weights
This subsection provides information about the dimensions and weights for modular cabinets and
enclosures installed in a modular cabinet and covers these topics:
• “Service Clearances for the Modular Cabinet” (page 57)
• “Unit Sizes” (page 57)
• “Modular Cabinet Physical Specifications” (page 58)
• “Enclosure Dimensions” (page 58)
• “Modular Cabinet and Enclosure Weights With Worksheet” (page 59)
56 System Installation Specifications