NonStop NS16000 Series Planning Guide (H06.11+)
1
For RVU requirements for CLIMs, see Table 5 (page 116).
Modular Cabinet and Enclosure Weights With Worksheet
The total weight of each modular cabinet is the sum the weights of the cabinet plus each enclosure
installed in it. Use this worksheet to determine the total weight:
TotalWeightNumber of
Enclosures
Enclosure Type
kglbskglbs
148.832842U (single-phase with modular PDUs)
1
14932842U (three-phase with modular PDUs)
1
13730342U (three-phase with monitored PDUs)
1
50.8112NonStop Blade Element
32.870Processor switch
43.596LSU
2453DL385 G2 or G5 CLIM
2
2658DL380 G6 CLIM
2
8.619CLIM cable management Ethernet patch
panel
19.443MSA70 3GB protocol SAS disk enclosure
(empty)
1738D2700 6GB protocol SAS disk enclosure
(empty)
.20.52.5 in SAS HDD, 3GB protocol, 72 GB,
15K rpm
.4512.5 in SAS HDD, 3GB protocol, 146 GB,
10K rpm
.4512.5 in SAS HDD, 6GB protocol, 300 GB,
10K rpm
.24.522.5 in SAS SSD
.04.1Disk blank
90.7200IOAM
35.478Fibre Channel disk module
2.224.89Maintenance switch (Ethernet)
15.434Rackmount console system unit keyboard
and display
57126R5000 UPS
63139R5000 ERM
72.6160R5500 XR UPS
77.1170R5500 XR ERM
----Total
1
Modular cabinet weight includes the PDUs and their associated wiring and receptacles.
2
For RVU requirements for CLIMs, see Table 5 (page 116).
Dimensions and Weights 59