NonStop NS16000 Series Planning Guide (H06.11+)
Total (BTU/hour)Unit Heat (Btu/hour,
maximum)
Unit Heat (Btu/hour,
typical)
Number InstalledEnclosure Type
3117SAS 2.5 in., 10k rpm
HDD
2314SAS 2.5 in., 15k rpm
HDD
19.919.4SAS SSD
18081808IOAM
2
375375Fibre Channel disk
module (no disk)
5858Fibre Channel disk
drive
6868Maintenance switch
(Ethernet)
3
600600Rack-mounted system
console (NSCR4)
392358Rack-mounted system
console (NSCR110)
9696Rack-mounted
keyboard and display
1
Measured with three PICs installed and active.
2
Measured with 10 Fibre Channel ServerNet adapters installed and active.
3
Maintenance switch has only one plug. If a UPS is installed in the modular cabinet, the maintenance switch plug must
be connected to the extension bars on the right-side of the modular cabinet.
Operating Temperature, Humidity, and Altitude
Maximum Rate of Change
per Hour
Recommended Range
1
Operating Range
1
Specification
68° to 77° F (20° to 25° C)41° to 95° F (5° to 35° C)Temperature (all except
Fibre Channel disk module,
9° F (5° C) Repetitive
36° F (20° C) Nonrepetitive
CLIMs and SAS disk
enclosures
-50° to 95° F (10° to 35° C)Temperature (Fibre Channel
disk module, CLIMs, and
SAS disk enclosure)
1.8° F (1° C) Repetitive
5.4° F (3° C) Nonrepetitive
--15% to 80%,
noncondensing
Humidity
--0 to 10,000 feet (0 to
3,048 meters)
Altitude
2
1
Operating and recommended ranges refer to the ambient air temperature and humidity measured 19.7 in. (50 cm) from
the front of the air intake cooling vents.
2
For each 1000 feet (305 m) increase in altitude above 10,000 feet (up to a maximum of 15,000 feet), subtract 1.5° F
(0.83° C) from the upper limit of the operating and recommended temperature ranges.
Dimensions and Weights 61