NonStop NS16000 Series Planning Guide (H06.11+)
Figure 14 Example Duplex Configuration
Table 2 shows the weight, power, and thermal calculations for Cabinet One in Figure 14 (page 63).
Table 2 Cabinet One Load Calculations
BTU/hourTotal Volt-amps (VA)WeightHeight (U)QuantityComponent
Maximum
Power
Consumption
Typical
Power
Consumption
Maximum
Power
Consumption
Typical
Power
Consumption
kglbs
7984726823402130152336153NonStop
Blade
Element
(chassis
and 4P
processor
assembly)
15011501440440449641LSU with 8
logic
boards
136513654004006414062Processor
switch
18081808530530107235111IOAM
enclosure
(with 10
Fibre
Channel
ServerNet
adapters)
686820202511Maintenance
switch
----149328421Cabinet
127271201137303520518114037-Total
Calculating Specifications for Enclosure Combinations 63