NonStop NS2200 Series Planning Guide

If you are installing a single-cabinet row, you must install both the front and the side anti-tip
feet.
The use of anti-tip feet does not affect the service clearances required for the cabinet.
For more information about HP 10000 G2 racks, including stabilization, see:
HP 10000 G2 Series Rack User Guide
Best Practices for HP10000 Series and HP 10000 G2 Series Racks
For more information about HP Intelligent racks, including stabilization, see:
HP Intelligent Rack Family User Guide
HP Intelligent Rack Family Options Installation Guide
NOTE: 36U and 42U Intelligent racks can be used for NonStop NS2200 and NS2200T systems,
but not for NonStop NS2200ST systems. 36U and 42U G2 racks can coexist with 36U and 42U
Intelligent racks in NonStop NS2200 and NS2200T systems.
Use baying kits to bay G2 racks to G2 racks of the same height or Intelligent racks to Intelligent
racks of the same height. Use baying plates to bay Intelligent racks to G2 racks of the same height.
In all cases, a rack cannot be bayed with another rack of a different height.
Commercial Grade Cabinet Ground Connections
The site building must provide a power distribution safety ground/protective earth for all NonStop
system equipment. This safety grounding system must comply with local codes and any other
applicable regulations for the installation locale. For detailed information about grounding the
cabinet, ask your HP service provider to refer to the NS2200 Series Hardware Installation Manual.
Intracabinet Grounding for Commercial Grade Cabinets
A commercial grade cabinet has grounding points located throughout the cabinet. Ground cables
are green with a yellow stripe and are used to connect an enclosure to the cabinet grounding rail.
For detailed information about intracabinet grounding and ground connections, ask your HP service
provider to refer to the NS2200 Series Hardware Installation Manual.
Specifications for NonStop NS2200T System Components
NOTE: All specifications assume an enclosure that is fully loaded.
Blade Element CG (rx2800 i2)
For details about the rx2800 i2 server, see the HP Integrity rx2800 i2 Server User Service Guide
at http://h20000.www2.hp.com/bc/docs/support/SupportManual/c02722594/c02722594.pdf
Fuse Panel Specifications
ValueSpecification
Enclosure Dimensions
2UU Height
1.8 in (4.6 cm)Height
19 in (48.3 cm)Width
30.5 in (77.5 cm)Depth (including safety cover)
25 in (63.5 cm)Depth (without safety cover)
134 Specifications for NonStop NS2200T Systems