NonStop NS2200 Series Planning Guide
Fuse Panel Specifications
ValueSpecification
Enclosure Dimensions
2UU Height
1.8 in (4.6 cm)Height
19 in (48.3 cm)Width
30.5 in (77.5 cm)Depth (including safety cover)
25 in (63.5 cm)Depth (without safety cover)
Enclosure Weight
16 lbs (7.3 kg)Weight, unboxed
Outputs
4Number of TPA (maximum 50A rating) outputs per power
rail
5Number of GMT (maximum 15A rating) outputs per power
rail
80AMax total load rating
Input requirements
-48/-60 VDCNominal voltage
-36VDC to -72VDCOperating voltage
80A per inputMax input rating
2Total inputs
As appropriate for maximum total load rating.Site branch circuit protection
Heat Dissipation
1
239 BTU/hourUnit heat (single line powered)
479 BTU/hourUnit heat (both lines powered)
1
Maximum value. Assumes full load per side of 70W
Fuse Panel Ground Connections
The fuse panel requires a separate ground connection from the chassis to the cabinet grounding
rail. The fuse panel has two grounding locations at the bottom of the panel. Ground cables connect
from these points to the ground rails. Ask your HP service provider to refer to the NS2200 Series
Hardware Installation Manual for detailed information about connecting these ground cables.
VIO Enclosure (DC-Powered) Specifications
ValueSpecification
Enclosure Dimensions
4 UU Height
6.9 in (17.5 cm)Height
19 in (48.3 cm)Width
27 in (68.6 cm)Depth
144 Specifications for NonStop NS2200ST Systems










