NonStop NS2200 Series Planning Guide
ValueSpecification
Enclosure Weight
62 lbs (28 kg)Unboxed, fully loaded
Power and Heat
2Number of power inputs
326 WMaximum power consumption
894 BTU/hourNominal heat dissipation
1112 BTU/hourMaximum heat dissipation
NS2200ST CLIM Specifications
DL380p Gen8 CLIM CG ValueDL380 G6 CLIM CG ValueSpecification
Enclosure Dimensions
2 U2 UU Height
3.4 in (8.6 cm)3.4 in (8.6 cm)Height
17.5 in (44.5 cm)17.5 in (44.5 cm)Width
27.3 in (69.2 cm)27.3 in (69.2 cm)Depth
Enclosure Weight
63 lbs (28.6 kg)62 lbs (28 kg)Unboxed
Power and Heat
22Number of power inputs
130 W234 WTypical power consumption
160 W308 WMaximum power consumption
444 BTU/hour794 BTU/hourTypical heat dissipation
546 BTU/hour1051 BTU/hourMaximum heat dissipation
CLIM Ground Connections
All DC-powered CLIMs have a ground plate that is mounted on the back of the enclosure. The
ground plate provides one threaded stud for the ground cable lug. The other end of the ground
cable connects to the cabinet grounding rail.
In addition, there is a ground cable in the unterminated end of DC input power cable that connects
from the power supply to the fuse panel or breaker panel. The ground cable in this cable must also
connect to the cabinet grounding rail. Ask your HP service provider to refer to the CLuster I/O
Module (CLIM) Installation and Configuration Guide for detailed information about connecting
these ground cables.
Disk Enclosure Specifications
M8391-24CG and M8392-24CG ValueSpecification
Enclosure Dimensions
2 UU Height
3.5 in (8.9 cm)Height
Specifications for NonStop NS2200ST System Components 145