NonStop NS2200 Series Planning Guide
Enclosure Locations in Cabinets
This table provides details about the required locations of NonStop NS2200 and NS2200ST
system enclosures and components within a cabinet. The enclosure location refers to the U location
on the rack where the lower edge of the enclosure resides, such as the bottom of an rx2800 i2
blade element at 11U.
• “Enclosure Locations in NS2200T Commercial Grade Cabinets”
• “Enclosure Locations in NS2200ST Cabinets” (page 160)
This table only applies to configurations that use the NS2200T commercial grade cabinet.
Table 15 Enclosure Locations in NS2200T Commercial Grade Cabinets
Notes
Required Cabinet (Rack)
LocationHeight (U)Enclosure or Component
Required when you have less
than four cabinets bayed
Bottom front exterior of
cabinet
N/ACabinet stabilizer
together. Cabinet stabilizer
is not required when cabinet
is bolted to its adjacent
cabinet.
U1 for the first blade
element.
2UBlade element
2UFuse panel U35 in a 4 processor system
U33 in a 2 processor system
U17 for the first VIO
enclosure.
4UVIO enclosure
SAS disk enclosures should
be near or adjacent to the
Storage CLIMs.
U13 for the first SAS CG
disk enclosure.
2USAS CG disk enclosure
Storage CLIM CGs should
be near or adjacent to one
another in groups of two.
U9 for the first Storage CLIM
CG.
2UStorage CLIM CG
IP or Telco CLIMs should be
adjacent to one another in
Any available 2U space that
is not required by other
2UIP or Telco CLIM CG
groups of two, so the CLIMscomponents. Upper U
locations are recommended. can easily connect to the
ports on the VIO enclosure.
Top 1U space located at
rear of cabinet
1UCLIM patch panel CG
If a second CG maintenance
switch is used, install it
1UCG Maintenance switch U38 in a 42U cabinet.
U32 in a 36U cabinet.
below the first maintenance
switch.
Enclosure Locations in Cabinets 159