NonStop NS2200 Series Planning Guide

This table only applies to configurations that use the NS2200ST seismic rack.
Table 16 Enclosure Locations in NS2200ST Cabinets
NotesRequired Cabinet (Rack)
Location
Height (U)Enclosure or Component
Required when you have less
than four cabinets bayed
Bottom front exterior of
cabinet
N/ACabinet stabilizer
together. Cabinet stabilizer
is not required when cabinet
is bolted to its adjacent
cabinet.
U1 for the first blade
element.
2UBlade element
2UFuse panel U35 in a 4 processor system
U33 in a 2 processor system
U18 for the first VIO
enclosure.
4UVIO enclosure
SAS disk enclosures should
be near or adjacent to the
Storage CLIMs.
U13 for the first SAS CG
disk enclosure
2USAS CG disk enclosure
U17 is reserved for the
seismic rack-mount kit.
U171USeismic rack-mount kit
Storage CLIMs must be
adjacent to one another.
U9 for the first Storage
CLIM.
2UStorage CLIM CG
IP or Telco CLIMs should be
adjacent to one another in
Any available 2U space that
is not required by other
2UIP or Telco CLIM CG
groups of two, so the CLIMscomponents. Upper U
locations are recommended. can easily connect to the
ports on the VIO enclosure.
Top 1U space located at
rear of cabinet
1UCLIM patch panel CG
If a second CG maintenance
switch is used, install it
1UCG Maintenance switch U41 in a 42U G2 cabinet
(NS2200T)
below the first maintenance
switch.
U35 in a 36U cabinet.
U32 in a seismic rack
160 Hardware Configuration in NS2200T and NS2200ST Cabinets