NonStop NS2200 Series Planning Guide
NonStop System With Two Rack-Mounted UPS in Parallel
Figure 65 shows an example of a non-supported configuration in a NonStop system with the left
PDUs connected to a rack-mounted UPS, and the right PDUs connected to a different rack-mounted
UPS. In this configuration, OSM manages and monitors the rack-mounted UPSs.
Figure 65 NonStop System With Two Rack-Mounted UPS in Parallel
OSM has the capability to monitor both UPSs, but it does not have the logic to initiate the controlled
shutdown of the I/O operations and processors when utility power fails in this configuration.
• If the utility power is not restored before both rack-mounted UPSs shut down, any data in the
NonStop system disk drive write cache that has not been transferred to the disk drive media
is lost.
If you want to extend the UPS battery runtime, HP recommends adding the Extended Runtime
Modules (ERMs) to the UPS.
Non-Supported UPS Configurations 207