NonStop NS2200 Series Planning Guide

There are two different versions of the R5000 single-phase UPS:
For North America and Japan, the HP AF460A is utilized and uses a NEMA L6-30P (30A)
input connector with 200 to 208V single-phase.
For International, the HP AF461A is utilized and uses an IEC-60309 (32A) input connector
with 220V to 240V AC single-phase power.
NOTE: The AC input power cord for the single-phase UPS is routed to exit the modular cabinet
at either the top or bottom rear corners of the cabinet, depending on what is ordered for the site
power feed (the large output receptacle is unused).
For the UPS power and environmental requirements, see “System Installation Specifications for
NonStop NS2200 Systems” (page 56). For planning, installation, and emergency power-off (EPO)
instructions, see the HP UPS R5000 User Guide at:
http://h20000.www2.hp.com/bc/docs/support/SupportManual/c02945229/c02945229.pdf
and the HP UPS Network Module User Guide at:
http://bizsupport2.austin.hp.com/bc/docs/support/SupportManual/c02864927/c02864927.pdf
For other UPSs, refer to the documentation shipped with the UPS.
UPS for a Three-Phase Power Configuration (Optional)
HP supports the HP model R12000/3 UPS for the three-phase power configuration because it
utilizes the power fail support provided by OSM for this configuration. For information about the
requirements for installing a UPS, see “Uninterruptible Power Supply (UPS)” (page 52).
There are two different versions of the R12000/3 UPS:
For North America and Japan, the HP AF429A is utilized and uses an IEC309 560P9 (60A)
input connector with nominal 208V 3-phase Wye.
For International, the HP AF430A is utilized and uses an IEC309 532P6 (32A) input connector
with nominal 400V 3-phase Wye).
NOTE: The R12000/3 UPS has two output connectors.
For the R12000/3 UPS power and environmental requirements, see Chapter 4 (page 56). For
planning, installation, and emergency power-off (EPO) instructions, see the HP 3 Phase UPS User
Guide at:
http://bizsupport.austin.hp.com/bc/docs/support/SupportManual/c01079392/c01079392.pdf
For other UPSs, refer to the documentation shipped with the UPS.
ERM (Optional with UPS)
Cabinet configurations that include the HP UPS can also include extended runtime modules (ERMs).
An ERM is a battery module that extends the overall battery-supported system run time. Up to two
ERMs can be used for even longer battery-supported system run time.
NonStop NS2200 Hardware 37