NonStop NS2200 Series Planning Guide

voltage of AC power at the intended installation site for the system. For information on the PDUs
supported for a NonStop NS2200 system, see AC Input Power for Modular Cabinets” (page 71).
Uninterruptible Power Supply (UPS)
A NonStop NS2200 system can use the HP model R5000 UPS for a single-phase power
configuration or the HP model R12000/3 UPS for a three-phase power configuration. An extended
run-time module (ERM) can be combined with either UPS to extend battery time.
AC Input Power for Modular Cabinets
This subsection provides information about AC input power for NonStop NS2200 modular cabinets.
Table 2 (page 71) contains the single-phase power specifications for the power components
used in North America and Japan.
Table 3 (page 72) contains the single-phase power specifications for the power components
used in North America and Japan.
Table 4 (page 72) contains the single-phase power specifications for the power components
used in international installations.
Table 5 (page 72) contains the single-phase power specifications for the power components
used in international installations.
CAUTION: Be sure the hardware configuration and resultant power loads of each cabinet within
the system do not exceed the capacity of the branch circuit according to applicable electrical codes
and regulations.
Select circuit breaker ratings according to local codes and any applicable regulations for the circuit
capacity. Note that circuit breaker ratings vary if your system includes an optional rack-mounted
UPS.
Table 2 North America/Japan Single-Phase Power Specifications
Modular PDU 1-phaseiPDU 1-phaseR5000 1-phase UPS
24 A24 A4500 WOutput Load
200 – 240 V200 – 208 V200 – 208 VInput Voltage
NEMA L6-30PNEMA L6-30PNEMA L6-30PInput Connector
N/AN/A200 – 208 VOutput Voltage
4 x C196 x C191 x L6-30ROutput Connectors
(28 x C13)(20 x C13)4 x C19
4 x C13
UPS outputs are connected to the compatible PDU inputs.Notes
AC Input Power for Modular Cabinets 71