NonStop NS2200 Series Planning Guide

Table 5 International Three-Phase Power Specifications (continued)
Modular PDU 3-phaseiPDU 3-phaseR12000 3-phase UPS
N/AN/A400V 3P WyeOutput Voltage
6 x C19 (20 A)6 x C192 x IEC309 309 516C6Output Connectors
(42 x C13)(20 x C13)
UPS outputs are connected to the compatible PDU inputs.Notes
Enclosure AC Input
NOTE: For instructions on grounding the modular cabinet rack by using the HP Rack Grounding
Kit (AF074A), ask your HP service provider to refer to the instructions in the HP 10000 G2 Series
Rack Options Installation Guide at:
http://bizsupport1.austin.hp.com/bc/docs/support/SupportManual/c01493702/c01493702.pdf
NOTE: For instructions on grounding the modular cabinet Intelligent rack using the HP Intelligent
Rack Ground Bonding Kit (BW891A), ask your HP service provider to refer to the instructions in
the HP Intelligent Rack Family Options Installation Guide at:
http://h20565.www2.hp.com/portal/site/hpsc/public/psi/manualsResults/?sp4ts.oid=5193884
Enclosures (blade element, VIO enclosure, and so forth) require:
ValueSpecification
200/208/220/230/240 V AC RMSNominal input voltage
180-264 V ACVoltage range*
50 or 60 HzNominal line frequency
47-53 Hz or 57-63 HzFrequency ranges
1Number of phases
* Voltage range for the VIO enclosure is 100-240 V AC, and for the maintenance switch is 200-240 V AC.
Each PDU is wired to distribute the load segments to its receptacles. For more information, see
“Power Distribution for NonStop NS2200 Systems In Intelligent Racks” (page 56). Factory-installed
enclosures are connected to the PDUs for a balanced load among the load segments.
CAUTION: If you are installing NonStop NS2200 system enclosures in a rack, balance the current
load among the available load segments. Using only one of the available load segments, especially
for larger systems, can cause unbalanced loading and might violate applicable electrical codes.
Connecting the two power plugs from an enclosure to the same load segment causes failure of the
hardware if that load segment fails.
Enclosure Power Loads
The total power and current load for a modular cabinet depends on the number and type of
enclosures installed in it. Therefore, the total load is the sum of the loads for all enclosures installed.
AC Input Power for Modular Cabinets 73