NonStop NS2200 Series Planning Guide
For examples of calculating the power and current load for various enclosure combinations, see
“Calculating Specifications for Enclosure Combinations” (page 86).
In normal operation, the AC power is split equally between the two PDUs in the modular cabinet.
However, if one of the two AC power feeds fails, the remaining AC power feed and PDU must
carry the power for all enclosures in that cabinet.
Power and current specifications for each type of enclosure are:
Peak Inrush Current (amps)Maximum Power
Consumption
(Watts)
Typical Power
Consumption (Watts)
AC Power Lines per
Enclosure
1
Enclosure Type
-469 (8 GB)275 (8 GB)2Blade element (rx2800
i2)
486 (16 GB)292 (16 GB)
501 (32 GB)304 (32 GB)
303262622VIO enclosure
-2251352
DL380 G6 Storage
CLIM
-1601302
DL380p Gen8 Storage
CLIM
-2001302DL380 G6 IP CLIM
-1561262
DL380p Gen8
Networking CLIM 5
copper ports (IP or
Telco)
-1581282
DL380p Gen8
Networking CLIM 3
copper/2 optical ports
(IP or Telco)
5125752
M8381-25 SAS disk
enclosure (no disks)
-95-SAS disk drive 10k rpm
-74-SAS disk drive 15k rpm
-66-
200GB SAS 2.5” SSD,
Gen1
-66-
200GB SAS 2.5” SSD,
Gen2
-1151051Rack-mounted system
console (NSCR210 or
NSCR212 )
228281Rack-mounted keyboard
and monitor
420201Maintenance switch
(Ethernet)
2
1
Half of the plugs for an enclosure must be connected to a left-side extension bar and the other half connected to a
right-side extension bar. PDUs must be supplied from separate branch circuits.
2
Maintenance switch has only one plug. If a UPS is installed in the modular cabinet, the maintenance switch plug must
be connected to the extension bar on the left side of the modular cabinet.
74 System Installation Specifications for NonStop NS2200 Systems